Worked example
This page walks end-to-end through configuring a small but realistic EtherCAT segment in Autonomy Edge. The hardware is a Beckhoff EK1100 coupler followed by mixed digital and analog terminals, which is the most common starting point for EtherCAT in industrial deployments. Every step uses the editor exactly as it is, no custom scripting.
What we are building
| Position | Device | Function | I/O |
|---|---|---|---|
| 1 | Beckhoff EK1100 EtherCAT Coupler (2A E-Bus) | Bus coupler | None. Passes E-bus to terminals downstream |
| 2 | Beckhoff EL1809 16-channel digital input | 16 24V digital inputs | %IX0.0 -- %IX1.7 |
| 3 | Beckhoff EL2809 16-channel digital output | 16 24V digital outputs | %QX0.0 -- %QX1.7 |
This matches the segment used in the screenshots throughout the EtherCAT pages.
The wiring is a single CAT5e cable from the Linux host's dedicated NIC into the EK1100's IN port. The downstream terminals plug into the coupler's E-bus side. No managed switch is present.
Step 1: Prerequisites
Before opening the editor, make sure the host meets the Prerequisites:
- Runtime v4 on Linux.
- A second NIC dedicated to EtherCAT, separate from the host's management network.
- The EtherCAT NIC connected to the EK1100's IN port. The EK1100 is powered.
Plug the cable in, confirm the EK1100 link LED is solid, and continue.
Step 2: Add the EtherCAT bus to the project
- Open the project in the Autonomy Edge editor.
- Click the + next to the project name.
- Select Remote Device.
- Type
ethin Device name. - Choose EtherCAT from the Protocol dropdown.
- Click Create.
The bus appears under Remote Devices as eth. Click it to open the EtherCAT Bus Editor. The header reads EtherCAT Bus: eth with the subtitle EtherCAT Master Configuration. The Bus tab is selected by default.
Step 3: Upload the ESI files
The Beckhoff terminals are Beckhoff Automation devices, and Beckhoff publishes one ESI XML per terminal series. For our segment we need:
Beckhoff EK11xx.xml(covers the EK1100 family)Beckhoff EL1xxx.xml(covers the EL1809 along with the rest of the EL1xxx digital input series)Beckhoff EL2xxx.xml(covers the EL2809 along with the rest of the EL2xxx digital output series)
Download the three files from the Beckhoff website (search for "Beckhoff ESI files"), then:
- Switch to the Repository tab in the Bus Editor.
- Drag the three
.xmlfiles onto the ESI Device Files drop zone. The progress display shows each file as it parses. - When parsing finishes, the Loaded Files table shows the three files with a
Beckhoff Automation GmbH & Co. KG (0x2)vendor and the device count for each.
You should see something like:
codeLoaded Files (3) - 317 device(s) Beckhoff EK11xx.xml Beckhoff Automation GmbH & Co. KG (0x2) 24 Beckhoff EL1xxx.xml Beckhoff Automation GmbH & Co. KG (0x2) 155 Beckhoff EL2xxx.xml Beckhoff Automation GmbH & Co. KG (0x2) 138
The device counts will vary as Beckhoff publishes new revisions; the structure is the same.
Step 4: Set the master configuration
- Switch to the Advanced tab.
- Confirm ENABLE BUS is on.
- Leave CYCLE TIME (MICROSECONDS) at
1000. Three slaves on a clean segment is well within the default's headroom. - Leave TASK PRIORITY at
1for a development host. On a PREEMPT_RT industrial PC you can raise it later. - Leave WATCHDOG TIMEOUT (CYCLES) at
3.
These defaults are appropriate for a segment of this size. Save the project (Ctrl+S).
Step 5: Scan and add the slaves
- Switch back to the Bus tab.
- Confirm the Network Interface dropdown shows the NIC connected to the EK1100. If your second NIC is
enp4s0(typical on a desktop tower) oreth1(typical on a single-board computer), pick that one. Avoidloand your management interface. - Make sure the runtime is connected. The Scan button activates only when both the runtime is reachable and the EtherCAT discovery service is available.
- Click Scan. The button shows Scanning… while the master enumerates the segment. After a few seconds the Scanned Devices table fills in:
codePos Name Vendor Product 1 EK1100 EtherCAT Coupler (2A E-Bus) 0x0002 0x044C2C52 2 EL1809 16Ch. Dig. Input 24V, 3ms 0x0002 0x07113052 3 EL2809 16Ch. Dig. Output 24V, 0.5A 0x0002 0x0AF93052
Each row should be free of the No XML badge. If a row has it, the matching ESI is missing or its revision does not match. Re-check Step 3 and look at the slave's Device Info for the revision the wire is reporting.
- Tick the checkbox at the top of the table to select all three rows.
- Click Add Selected (3).
The three slaves move into the Configured Devices panel on the right. The project tree updates: under Remote Devices > eth you now see three child nodes:
EK1100 EtherCAT Coupler (2A E-Bus)EL1809 16Ch. Dig. Input 24V, 3msEL2809 16Ch. Dig. Output 24V, 0.5A
Step 6: Inspect the channel mappings
-
Click the
EL1809child node. The Slave Device Editor opens with the Channel Mappings tab selected. -
The toolbar shows
All (16),Inputs (16),Outputs (0). -
The table is pre-populated with 16 rows of
Input,BOOL, with addresses%IX0.0through%IX1.7. -
The Alias column is empty. Optionally fill in human-readable names:
pump_running,tank_level_high,e_stop_status, and so on. -
Click the
EL2809child node. Same layout, but every row isOutput,BOOL, with addresses%QX0.0through%QX1.7. The Inputs (0) / Outputs (16) filters confirm there are no inputs. -
Click
EK1100. Channel Mappings showsNo channels available for this device.. Couplers do not contribute process data, only mechanical and bus continuity. This is expected.
Step 7: Tune the per-slave configuration if needed
For this segment, the default per-slave configuration is correct. Spot-check one slave to be sure:
- Click
EL1809, then the Configuration tab. - Confirm Verify Vendor ID and Verify Product Code are both ticked (defaults).
- Addressing > EtherCAT Address =
0(auto, default). - Timeouts: SDO 1000, I → P 3000, P → S/S → O 10000. Defaults.
- Watchdog: SM Watchdog on at 100 ms; PDI Watchdog off at 100 ms. Defaults.
- Distributed Clocks (DC): Enable DC off. Defaults. Digital terminals do not need DC.
No edits required. Repeat for EL2809 if you want to be thorough; results are the same.
Step 8: Use the addresses in your program
With the segment configured, you can wire the I/O into Ladder, ST, or FBD code in the project. A trivial pump-control rung in Ladder:
The same logic in Structured Text:
pascalPROGRAM main VAR pump_running AT %IX0.0 : BOOL; tank_low AT %IX0.1 : BOOL; pump_relay AT %QX0.0 : BOOL; END_VAR pump_relay := pump_running AND NOT tank_low; END_PROGRAM
The %IX0.0, %IX0.1, %QX0.0 references resolve directly to the EL1809 input bits and the EL2809 output bit you mapped earlier. There is no separate "EtherCAT bind" step.
Step 9: Run
-
Save the project (Ctrl+S).
-
Compile and transfer the program to the runtime as you would for any project.
-
The runtime starts the EtherCAT bus on first program execution.
-
Watch the Diagnostics panel. Within a couple of seconds the master state should transition
IDLE → SCANNING → CONFIGURING → OPERATIONAL. The per-slave table should show all three slaves atOPwithErrors = 0. -
Toggle a 24V signal on one of the EL1809 inputs. The pump_relay output on the EL2809 should respond per your logic.
Adding more terminals later
The same flow extends naturally:
- For an additional terminal in the EL3xxx (analog input) family, download
Beckhoff EL3xxx.xmlto the repository and re-scan. The new slave appears at the next position withInputchannels ofINTorUINTtype mapped to consecutive%IWaddresses. - For an EL4xxx analog output, repeat with
Beckhoff EL4xxx.xml. Channels are mapped to%QW. - For mixed analog/digital terminals, the editor's IEC-type table in Channel Mappings shows the exact mapping.
The master cycle time (1000 µs default) handles up to a few dozen of these comfortably. Past that, follow the cycle-time floor table in Prerequisites to size the cycle for the segment.
What's next?
- Troubleshooting if any slave fails to reach OP
- Diagnostics for what to monitor while the bus is running
- Communication Protocols Overview to compare EtherCAT with the other supported protocols