Bistable Function Blocks
Bistable function blocks are memory elements. They remember whether they've been "set" or "reset" and hold that state until the opposite action occurs. In electrical terms, they behave like latching relays. Once energized, they stay on until explicitly turned off.
The IEC 61131-3 standard defines two bistable blocks, SR and RS, plus a SEMA (semaphore) block. All three are available in the Autonomy Edge web IDE under System Libraries.
The critical distinction between SR and RS is which input takes priority when both the set and reset inputs are TRUE at the same time. Understanding this difference is essential for writing safe, predictable control logic.
Declaring a Bistable Variable
To use a bistable block in your program:
- Open the Variables Table for your POU.
- Add a new variable (e.g.,
MotorLatch). - In the Type column, click the dropdown and select System Libraries.
- Choose
SR,RS, orSEMAfrom the list.
SR: Set-Reset (Set Dominant)
In the SR block, the set input dominates. If both S1 and R are TRUE simultaneously, the output Q1 will be TRUE. This makes SR the appropriate choice when it's more important to activate than to deactivate. For example, triggering a safety alarm that must remain active even if a reset condition happens to be true at the same time.
Inputs
| Name | Type | Description |
|---|---|---|
S1 | BOOL | Set input (dominant) |
R | BOOL | Reset input |
Outputs
| Name | Type | Description |
|---|---|---|
Q1 | BOOL | Latched output |
FBD Diagram
Logic Equation
codeQ1 := S1 OR ((NOT R) AND Q1)
This means:
- If
S1is TRUE,Q1is TRUE regardless ofR. - If
S1is FALSE andRis TRUE,Q1is FALSE. - If both are FALSE,
Q1retains its previous state.
Truth Table
| S1 | R | Q1 (previous) | Q1 (result) | Explanation |
|---|---|---|---|---|
| FALSE | FALSE | FALSE | FALSE | No change. Stays off |
| FALSE | FALSE | TRUE | TRUE | No change. Stays on |
| TRUE | FALSE | any | TRUE | Set wins |
| FALSE | TRUE | any | FALSE | Reset wins |
| TRUE | TRUE | any | TRUE | Set dominates |
Structured Text Example
iecstPROGRAM AlarmLatch VAR FaultDetected : BOOL; (* Sensor or logic fault condition *) AcknowledgeBtn : BOOL; (* Operator acknowledges and clears *) AlarmActive : BOOL; (* Alarm output to HMI and horn *) AlarmLatch : SR; (* Set-dominant: alarm cannot be silenced while fault exists *) END_VAR AlarmLatch(S1 := FaultDetected, R := AcknowledgeBtn); AlarmActive := AlarmLatch.Q1; END_PROGRAM
The alarm activates when a fault is detected. The operator can only clear the alarm by pressing acknowledge after the fault condition has been resolved. If the fault is still active when the operator presses acknowledge, the set input dominates and the alarm stays on.
RS: Reset-Set (Reset Dominant)
In the RS block, the reset input dominates. If both S and R1 are TRUE simultaneously, the output Q1 will be FALSE. This makes RS the appropriate choice when safety requires that the off-state takes priority. For example, a motor control where the stop command must always override the start command.
Inputs
| Name | Type | Description |
|---|---|---|
S | BOOL | Set input |
R1 | BOOL | Reset input (dominant) |
Outputs
| Name | Type | Description |
|---|---|---|
Q1 | BOOL | Latched output |
FBD Diagram
Logic Equation
codeQ1 := (NOT R1) AND (S OR Q1)
This means:
- If
R1is TRUE,Q1is FALSE regardless ofS. - If
R1is FALSE andSis TRUE,Q1is TRUE. - If both are FALSE,
Q1retains its previous state.
Truth Table
| S | R1 | Q1 (previous) | Q1 (result) | Explanation |
|---|---|---|---|---|
| FALSE | FALSE | FALSE | FALSE | No change. Stays off |
| FALSE | FALSE | TRUE | TRUE | No change. Stays on |
| TRUE | FALSE | any | TRUE | Set wins |
| FALSE | TRUE | any | FALSE | Reset wins |
| TRUE | TRUE | any | FALSE | Reset dominates |
Structured Text Example
iecstPROGRAM MotorControl VAR StartButton : BOOL; (* Momentary start pushbutton *) StopButton : BOOL; (* Momentary stop pushbutton *) MotorOutput : BOOL; (* Output to motor contactor *) MotorLatch : RS; (* Reset-dominant: stop always wins *) END_VAR MotorLatch(S := StartButton, R1 := StopButton); MotorOutput := MotorLatch.Q1; END_PROGRAM
The motor starts when the operator presses Start and stays running after the button is released (latched). Pressing Stop turns it off. If both buttons are pressed simultaneously, the stop command wins. A standard safety requirement in motor control.
Choosing Between SR and RS
The choice depends on your safety requirements:
| Scenario | Recommended Block | Reason |
|---|---|---|
| Motor start/stop | RS (Reset Dominant) | Stop must always override start |
| Alarm activation | SR (Set Dominant) | Alarm must not be silenced while the fault persists |
| Safety interlock | RS (Reset Dominant) | Safety shutdown must always take priority |
| Latching a request | SR (Set Dominant) | Request should persist until explicitly cleared |
Tip: If the output being ON represents a potentially dangerous state (like a motor running), use RS so that the off-command always wins. If the output being ON represents a protective state (like an alarm or interlock), use SR so that the protection can't be bypassed.
SEMA: Semaphore
The SEMA block implements a simple resource-locking mechanism. It has a CLAIM input and a RELEASE input, with a BUSY output that indicates whether the resource is currently claimed. Once claimed, subsequent claim attempts are ignored until the resource is released.
Inputs
| Name | Type | Description |
|---|---|---|
CLAIM | BOOL | Request to claim the resource |
RELEASE | BOOL | Request to release the resource |
Outputs
| Name | Type | Description |
|---|---|---|
BUSY | BOOL | TRUE when the resource is currently claimed |
FBD Diagram
Behavior
- When
CLAIMtransitions to TRUE and the resource is not busy,BUSYgoes TRUE. - When
RELEASEis TRUE,BUSYgoes FALSE. - If the resource is already busy, additional
CLAIMsignals are ignored.
Structured Text Example
iecstPROGRAM SharedPrinter VAR Station1Request : BOOL; (* Station 1 wants the printer *) Station1Done : BOOL; (* Station 1 finished printing *) PrinterBusy : BOOL; (* Printer is currently in use *) PrinterLock : SEMA; (* Semaphore for exclusive access *) END_VAR PrinterLock(CLAIM := Station1Request, RELEASE := Station1Done); PrinterBusy := PrinterLock.BUSY; END_PROGRAM
Common Bistable Patterns
Motor Start/Stop with Safety Interlock
Combine RS with an external safety condition:
iecst(* Motor can only start if guard is closed, stop always wins *) MotorLatch(S := StartBtn AND GuardClosed, R1 := StopBtn OR NOT GuardClosed); MotorRun := MotorLatch.Q1;
If the safety guard opens, the reset input goes TRUE and the motor stops immediately. The motor can't restart until the guard is closed again.
Alarm Latching with Acknowledgment
Use SR to create an alarm that must be acknowledged after the fault clears:
iecst(* Alarm stays active until BOTH: fault clears AND operator acknowledges *) AlarmLatch(S1 := FaultCondition, R := AckButton AND NOT FaultCondition); AlarmOutput := AlarmLatch.Q1;
The reset condition requires that the acknowledge button is pressed AND the fault is no longer present. This prevents operators from dismissing active faults.
What's Next?