Modbus addressing
When a Modbus client talks to your vPLC, it reads and writes Modbus addresses (coil 7, holding register 12, etc.). Your PLC program reads and writes IEC addresses (%QX0.0, %MW3, etc.). This page explains how the two map.
The rule, in one paragraph
Within each Modbus block (coils, discrete inputs, holding registers, input registers), the IEC segments you've configured for that block are laid out sequentially, starting at Modbus address 0 of that block. Sizes count in the addressable unit of that block: bits for coils and discrete inputs, 16-bit registers for holding and input registers. Bit addresses are formatted as [byte].[bit], so the 0th coil bit is %QX0.0, the 7th is %QX0.7, the 8th rolls over to %QX1.0.
That's it. The rest of this page is concrete examples.
Holding registers (FC 3 / 6 / 16)
Holding registers are 16-bit, read/write. The default segment layout exposes four IEC segments back-to-back:
| Modbus address | IEC | Size per IEC item |
|---|---|---|
0 … qwCount−1 | %QW0 … %QW(qwCount−1) | 1 register |
next mwCount | %MW0 … %MW(mwCount−1) | 1 register |
next mdCount × 2 | %MD0 … %MD(mdCount−1) | 2 registers each |
next mlCount × 4 | %ML0 … %ML(mlCount−1) | 4 registers each |
So if you have qwCount = 4, mwCount = 8, mdCount = 2, mlCount = 0:
| Modbus addr | IEC |
|---|---|
| 0 | %QW0 |
| 1 | %QW1 |
| 2 | %QW2 |
| 3 | %QW3 |
| 4 | %MW0 |
| 5 | %MW1 |
| … | … |
| 11 | %MW7 |
| 12, 13 | %MD0 (lo word, hi word) |
| 14, 15 | %MD1 |
The exact counts are set in the Modbus Server editor under Buffer Mapping → Holding Registers. Maximum 1024 registers per IEC segment.
Coils (FC 1 / 5 / 15)
Coils are single bits, read/write. The default segment layout exposes two IEC segments:
| Modbus address | IEC | Notes |
|---|---|---|
0 … qxBits−1 | %QX0.0 … %QX⌊(qxBits−1)/8⌋.((qxBits−1) mod 8) | byte.bit |
next mxBits | %MX0.0 … | same byte.bit rule |
Worked examples (default qxBits = 800):
| Modbus coil | IEC |
|---|---|
| 0 | %QX0.0 |
| 7 | %QX0.7 |
| 8 | %QX1.0 |
| 16 | %QX2.0 |
| 799 | %QX99.7 |
| 800 | %MX0.0 (first bit of the %MX segment) |
Maximum 8192 bits per IEC segment.
Discrete inputs (FC 2)
Read-only bits. One segment by default:
| Modbus address | IEC |
|---|---|
| 0 | %IX0.0 |
| 7 | %IX0.7 |
| 8 | %IX1.0 |
ixBits−1 | last bit of the segment |
Maximum 8192 bits.
Input registers (FC 4)
Read-only 16-bit registers. One segment by default:
| Modbus address | IEC |
|---|---|
| 0 | %IW0 |
| 1 | %IW1 |
iwCount−1 | last register |
Maximum 1024 registers.
The live address-mapping reference
The Modbus Server editor has an Address Mapping Reference accordion at the bottom that computes the full table at render time from your current buffer sizes. This is the source of truth, if you've changed the default segment sizes, look at that table, not at the defaults on this page.
Why %QX1.0 is coil 8, not coil 10
The bit numbering follows the byte/bit convention from IEC 61131-3 itself: %QX<byte>.<bit> where bit is 0…7. So %QX0.7 is the 8th bit of the segment (bit index 7), and %QX1.0 is the 9th bit (start of the next byte). Many off-the-shelf Modbus tools number coils 1-based (so coil 1 in the tool is coil 0 on the wire). Be careful which numbering your client uses.
What about %IB, %QB, %ID, %QD, %IL, %QL?
Modbus doesn't index byte / double / long input or output segments separately. If you have a %QD0 variable and you want it on Modbus, declare a %MD and copy the value across in your program, or use the S7Comm server (which does map all 14 PLC-memory variants directly). See S7Comm data blocks.
What's next
- Modbus server: configure the slave end (what's running on your vPLC).
- Modbus remote device: configure your vPLC as a master reading remote slaves.
- Worked example: Modbus slave: expose digital outputs.